Question 16

In accordance with ASHRAE Standard 170, general hospital Operating Rooms must have a minimum of two return grilles, one of which must be located:

Correct Answer: D
Comprehensive and Detailed Explanation:
OR Ventilation: ASHRAE Standard 170, Section 7.4.1, mandates at least two return/exhaust grilles in ORs, with one high and one low. The low grille (near the floor) removes heavier contaminants, while the high grille aids in overall air circulation, supporting laminar flow from ceiling diffusers.
Option Analysis:
A/B: Breathing height or anesthetizing location are not specified in ASHRAE 170.
C: Distance is practical but not the primary requirement.
D: Correct-high and low placement is explicitly required.
insert code

Question 17

In accordance with ASHRAE Standard 170, what is the MINIMUM outdoor air change rate for a patient room in a nursing unit?

Correct Answer: A
Comprehensive and Detailed Explanation:
Outdoor Air: ASHRAE 170, Table 7.1, specifies 2 ACH outdoor air minimum for patient rooms in nursing units, with a total of 6 ACH (remaining from recirculation).
insert code

Question 18

After coming into direct contact with medical instruments in a sterilizer, where should clean steam condensate that has been tempered be directed to?

Correct Answer: C
insert code

Question 19

How can negative air pressure BEST be maintained between the construction area and the occupied area of a hospital?

Correct Answer: A
insert code

Question 20

Which of the following represents the MINIMUM allowable area of non-aspirating diffuser required for a 400 sq. ft. (37.16 sq. m) Class C Operating Room with 1,267 CFM (598 L/s) air supply?

Correct Answer: B
Comprehensive and Detailed Explanation:
Class C OR Requirements: ASHRAE 170, Table 7.1, requires 20 ACH minimum, but diffuser sizing uses face velocity (25-35 fpm per Section 7.4.1).
Calculation: At 35 fpm (max recommended), Area = CFM / Velocity = 1,267 / 35 # 36.2 sq. ft.
Verification: 1,267 CFM over 36.2 sq. ft. = 35 fpm, meeting laminar flow criteria.
insert code
  • «
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • »
[×]

Download PDF File

Enter your email address to download ASHRAE.HFDP.v2026-02-25.q38 Dumps

Email:

FreeQAs

Our website provides the Largest and the most Latest vendors Certification Exam materials around the world.

Using dumps we provide to Pass the Exam, we has the Valid Dumps with passing guranteed just which you need.

  • DMCA
  • About
  • Contact Us
  • Privacy Policy
  • Terms & Conditions
©2026 FreeQAs

www.freeqas.com materials do not contain actual questions and answers from Cisco's certification exams.