Question 31

Given: A nonsprinklered commercial Type II-B building has a fire flow requirement of 7,000 gpm. If a sprinkler system is installed throughout the building, the new required fire flow is at least ___ gpm. (Assume that the new required fire flow is sufficient to meet the requirements of the sprinkler system.)

Correct Answer: A
IFC Section 903.3.5 and Appendix B (Fire-Flow Requirements) allow a reduction in fire flow when sprinklers are installed. For a Type II-B building (noncombustible, unprotected), the base fire flow (7,000 gpm) reflects a large, unsprinklered structure (e.g., per Table B105.1(2)). With full sprinkler protection, IFC B105.2 permits a reduction to as low as 25% of the original flow or the sprinkler demand (whichever is greater), typically
1,500 gpm for commercial buildings per NFPA 13 standards, assuming adequate water supply. Options B, C, and D exceed this minimum without justification. Thus, A is correct.
insert code

Question 32

Compressed natural gas (CNG) motor vehicle fuel-dispensing equipment may be installed in which of the following locations?

Correct Answer: C
Compressed Natural Gas (CNG) motor vehicle fuel-dispensing equipment installation requirements are outlined in 2021 International Fire Code (IFC) Section 2208 - Compressed Natural Gas Motor Fuel- Dispensing Facilities.
IFC 2021, Section 2208.3 - Equipment Location and Protection:
Requires that CNG dispensing equipment be installed at least:
10 feet from property lines
20 feet from public streets, highways, sidewalks, or railroads
10 feet from buildings or structures
Why Other Options Are Incorrect?
A: 40 ft. from trolley wires.
The IFC does not specify a 40-ft requirement for trolley wires in relation to CNG fuel-dispensing equipment.
B: 15 ft. from a public street.
Incorrect because IFC 2208.3 states that the minimum required distance from a public street is 20 feet, not 15 feet.
D: 5 ft. from an undeveloped property line.
Incorrect, as the minimum clearance from any property line is 10 feet, not 5 feet.
insert code

Question 33

What fire-resistance rating is required for interior nonbearing walls and partitions in Type IV construction?

Correct Answer: A
Fire-Resistance Rating for Nonbearing Walls in Type IV Construction
Type IV (Heavy Timber) construction, as defined by the International Building Code (IBC) 2021, Section
602.4, consists of large, solid or laminated wood members.
Interior nonbearing walls and partitions in Type IV construction are not required to have a fire-resistance rating (0 hours) unless they separate different occupancies or are specifically mandated by another code provision.
2. Why Type IV Does Not Require a Rating for Nonbearing Walls
The heavy timber components inherently provide fire resistance due to their large cross-section, which chars on the surface and slows fire penetration.
IBC Table 601 confirms that interior nonbearing walls in Type IV construction do not have a required fire- resistance rating.
3. Verification of Other Options
Option B (1 hour) - Incorrect, as Type IV does not require a 1-hour rating for interior nonbearing walls unless specific conditions apply.
Option C (1-1/2 hours) - Incorrect, as there is no code requirement for this level of rating in Type IV nonbearing walls.
Option D (2 hours) - Incorrect, as Type IV walls are not rated unless separating occupancies.
Reference Sources:
International Building Code (IBC) 2021 - Section 602.4 (Type IV Construction Requirements) IBC Table 601 (Fire-Resistance Ratings for Building Elements) ICC Fire Inspector II Study Guide (2021)
insert code

Question 34

What is the occupant load of a 50,000 gross square foot airport terminal concourse?

Correct Answer: D
To determine the occupant load of a 50,000 gross square foot airport terminal concourse, we use the occupant load factor from 2021 IBC Table 1004.5.
Step 1: Identify the Occupant Load Factor for an Airport Concourse
According to IBC Table 1004.5, the occupant load factor for an airport terminal concourse is 20 sq. ft. per person (gross).
Step 2: Calculate the Occupant Load
50,00020=2,500 occupants\frac{50,000}{20} = 2,500 \text{ occupants}2050,000=2,500 occupants Reference to Fire Inspector Documentation:
1. 2021 International Building Code (IBC) - Table 1004.5 (Occupant Load Factor for Airport Concourses)
20 sq. ft. per person is assigned for airport concourses.
2. 2021 International Fire Code (IFC) - Section 1004.1.2 (Occupant Load Determination) Gross area calculations must follow the correct occupant load factor per IBC Table 1004.5.
Detailed Explanation of Answer Choices:
Option A (Incorrect): 200 is too low based on proper calculations.
Option B (Incorrect): 500 is also too low.
Option C (Incorrect): 1,000 is below the required calculation.
Option D (Correct): 2,500 is the correct calculation based on IBC Table 1004.5.
Thus, the correct and verified answer is: D. 2,500.
insert code

Question 35

What fire-resistance rating is required for interior nonbearing wall and partitions in Type IV construction?

Correct Answer: A
The fire-resistance rating requirements for different building elements in Type IV (Heavy Timber) construction are specified in the 2021 International Building Code (IBC), Table 601 - Fire-Resistance Rating Requirements for Building Elements (Hours).
IBC Table 601 - Fire Resistance for Type IV Construction:
Interior nonbearing walls and partitions in Type IV construction require 0 hours of fire resistance.
This is because Type IV construction primarily relies on large, heavy timber elements that provide inherent fire resistance.
Why Other Options Are Incorrect?
B: 1 hour - Incorrect, as nonbearing interior walls in Type IV construction are not required to have a fire- resistance rating.
C: 1-1/2 hours - Not required by code.
D: 2 hours - Only structural elements like exterior walls in some cases may require fire resistance, but nonbearing interior partitions do not.
insert code
  • «
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • »
[×]

Download PDF File

Enter your email address to download InternationalCodeCouncil.Fire-Inspector-II.v2026-11-13.q41 Dumps

Email:

FreeQAs

Our website provides the Largest and the most Latest vendors Certification Exam materials around the world.

Using dumps we provide to Pass the Exam, we has the Valid Dumps with passing guranteed just which you need.

  • DMCA
  • About
  • Contact Us
  • Privacy Policy
  • Terms & Conditions
©2026 FreeQAs

www.freeqas.com materials do not contain actual questions and answers from Cisco's certification exams.