Question 36

The minimum fire-flow for a 75,000-sq. ft. building of Type IIB construction without a sprinkler system is:

Correct Answer: C
Reference to Fire-Flow Requirements for Type IIB Buildings:
The International Fire Code (IFC 2021), Appendix B, Table B105.1(2) establishes the minimum fire-flow requirements for buildings based on construction type, size, and the presence of sprinkler systems.
For a 75,000 sq. ft. Type IIB (non-combustible, unprotected) building without sprinklers, the required fire- flow is 5,500 gpm for 4 hours.
Why Fire-Flow Matters:
Fire-flow ensures that sufficient water is available to control and extinguish fires in large buildings.
Type IIB buildings lack built-in fire resistance enhancements, making adequate fire-flow crucial.
Clarification of Incorrect Answer Choices:
A: 3,000 gpm for 3 hours # Incorrect
Too low for a building of this size and construction type.
B: 4,000 gpm for 4 hours # Incorrect
Below the required 5,500 gpm per IFC Appendix B.
D: 5,750 gpm for 4 hours # Incorrect
Slightly above the requirement but not the exact minimum mandated by IFC Table B105.1(2).
Conclusion:
The correct and verified answer is C (5,500 gpm for 4 hours) as per IFC Appendix B, Table B105.1(2), ensuring compliance with fire-flow standards for Type IIB buildings without sprinklers.
insert code

Question 37

An acceptance test for a fire alarm system in a new apartment building should be scheduled after:

Correct Answer: B
IFC Section 901.5 (Acceptance Tests) requires fire protection systems, including fire alarms, to be tested upon completion to ensure compliance with NFPA 72 (National Fire Alarm and Signaling Code) and the IFC. The contractor's verification of full compliance (B) signals readiness for the official acceptance test by the fire code official, ensuring all components are installed and functional. Option A (zone-by-zone testing) is impractical for final acceptance. Option C ties the test to water supply, irrelevant to alarms. Option D (one year) is excessive and not required by IFC or NFPA 72 for initial acceptance. Thus, B is correct.
insert code

Question 38

A building under construction which has two stairways shall have a minimum of how many fire extinguishers per floor?

Correct Answer: B
Reference to Fire Extinguisher Requirements in Buildings Under Construction:
NFPA 241 (Standard for Safeguarding Construction, Alteration, and Demolition Operations) Section 13.6.1 and IFC 3309.1 require that:
A minimum of one fire extinguisher per floor is required.
Additional extinguishers are required based on stairwells and floor area.
If a building under construction has two stairways, a minimum of two fire extinguishers must be provided per floor to ensure adequate fire protection coverage.
Fire Safety Considerations for Construction Sites:
Construction sites pose a high fire risk due to temporary electrical systems, combustible materials, and lack of finished fire suppression systems.
Fire extinguishers must be readily available and evenly distributed near exit stairways and pathways for rapid access in case of an emergency.
Clarification of Incorrect Answer Choices:
A: 1 # Incorrect
One extinguisher is the minimum required for floors with only one exit/stairway, but a building with two stairways requires at least two extinguishers.
C: 3 # Incorrect
While more extinguishers can be added for larger areas or high-risk work zones, the minimum requirement remains two for two stairwells.
D: 4 # Incorrect
There is no general requirement for four extinguishers per floor unless dictated by floor size and hazard level.
Conclusion:
The correct and verified answer is B (2 fire extinguishers per floor) based on NFPA 241 and IFC 3309.1, ensuring compliance with fire safety standards for buildings under construction.
insert code

Question 39

The maximum combined quantity of Class II and III liquids which may be stored in a flammable liquids storage cabinet is __ gallons.

Correct Answer: C
Reference to Flammable Liquids Storage Cabinet Requirements:
According to The International Fire Code (IFC 2021), Section 5704.3.2 and NFPA 30 (Flammable and Combustible Liquids Code), Section 9.5.3, the maximum amount of Class II and Class III liquids that can be stored in a flammable liquids storage cabinet is 120 gallons.
This limit ensures safe containment, fire protection, and reduced risk of liquid ignition or spillage.
Understanding Class II and III Liquids:
Class II liquids: Flash point between 100°F and 140°F (e.g., diesel fuel, kerosene).
Class III liquids: Flash point above 140°F (e.g., motor oil, cooking oils).
While these liquids are less volatile than Class I liquids, they still pose a fire risk, requiring proper storage in approved cabinets.
Clarification of Incorrect Answer Choices:
A: 10 gallons # Incorrect
Too low; IFC and NFPA allow up to 120 gallons in storage cabinets.
B: 60 gallons # Incorrect
This is the maximum for Class I liquids, but Class II and III liquids are allowed up to 120 gallons.
D: 240 gallons # Incorrect
Exceeds the allowable limit per IFC 5704.3.2 and NFPA 30, which set the maximum at 120 gallons per cabinet.
Conclusion:
The correct and verified answer is C (120 gallons) as per IFC 5704.3.2 and NFPA 30, ensuring compliance with flammable liquids storage safety standards.
insert code

Question 40

A permit is required for storage of high-pile combustible stock in a building when the area of stock exceeds

Correct Answer: B
High-Pile Combustible Storage Permit Requirements
According to the International Fire Code (IFC) 2021, Section 105.6.23, a permit is required for the storage of high-pile combustible stock when the storage area exceeds 2,500 square feet.
2. Definition of High-Pile Storage
High-pile storage is defined as storage of combustible materials on racks or piles exceeding 12 feet in height (or 6 feet for highly combustible materials, such as rubber and plastics).
IFC Table 3206.2 establishes fire protection requirements based on storage height, area, and commodity class.
3. Verification of Other Options
Option A (225 sq. ft.) - Incorrect, as this is far below the 2,500 sq. ft. permit threshold.
Option B (500 sq. ft.) - Incorrect, as the fire code does not require a permit at this level.
Option C (1,000 sq. ft.) - Incorrect, as the IFC specifies 2,500 sq. ft. as the threshold for requiring a permit.
Reference Sources:
International Fire Code (IFC) 2021 - Section 105.6.23 (High-Pile Combustible Storage Permit Requirements) IFC Chapter 32 (High-Piled Storage Regulations) ICC Fire Inspector II Study Guide (2021) Thus, the correct and verified answer is: D. 2,500. #
insert code
  • «
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • »
[×]

Download PDF File

Enter your email address to download InternationalCodeCouncil.Fire-Inspector-II.v2026-11-13.q41 Dumps

Email:

FreeQAs

Our website provides the Largest and the most Latest vendors Certification Exam materials around the world.

Using dumps we provide to Pass the Exam, we has the Valid Dumps with passing guranteed just which you need.

  • DMCA
  • About
  • Contact Us
  • Privacy Policy
  • Terms & Conditions
©2026 FreeQAs

www.freeqas.com materials do not contain actual questions and answers from Cisco's certification exams.